Specification
DEHNbloc® modular
DB M 1 255 FM (961 125)
■ Coordinated spark-gap-based lightning current arrester consisting of a base part and a plug-in protection module
■ Maximum system availability due to RADAX Flow follow current limitation
■ Without additional cable length directly coordinated with DEHNguard surge protective device
Coordinated and modular single-pole lightning current arrester with high follow current limitation; with remote signalling contact for the monitoring system (floating changeover contact).
SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Nominal voltage (a.c.) (UN) 230 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) (UC) 255 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp) 50 kA
Specific energy (W/R) 625.00 kJ/ohms
Voltage protection level (UP) ≤ 2.5 kV
Follow current extinguishing capability (a.c.) (Ifi) 50 kArms
Follow current limitation / Selectivity
no tripping of a 32 A gG fuse up to 50 kArms (prosp.)
Response time (tA) ≤ 100 ns
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s) 500 A gG
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s) 315 A gG
Max. backup fuse (L-L') 125 A gG
Temporary overvoltage (TOV) (UT) – Characteristic 440 V / 120 min. – withstand
Operating temperature range (parallel connection) (TUP) -40 °C ... +80 °C
Operating temperature range (series connection) (TUS) -40 °C ... +60 °C
Operating state / fault indication green / red
Number of ports 1
Cross-sectional area (L/N, L'/N', N/PE (N)) (min.) 10 sq-mm. solid / flexible
Cross-sectional area (L/N, N/PE(N)) (max.) 50 sq-mm.
Cross-sectional area (L'/N') (max.) 35 sq-mm.
2 stranded / 25 sq-mm flexible
For mounting on 35 mm DIN rails acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Place of installation indoor installation
Degree of protection IP 20
Capacity 2 module(s), DIN 43880
Approvals VDE, KEMA, UL
Type of remote signalling contact changeover contact
Switching capacity (a.c.) 250 V / 0.5 A
Switching capacity (d.c.) 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 sq-mm. solid / flexible
Use in switchgear installations with prospective short-circuit
Max. prospective short-circuit current 100 kArms (220 kApeak)
Limitation / Extinction of mains follow currents up to 100 kArms (220 kApeak)
Max. backup fuse (L) up to IK = 100 kArms (ta ≤ 0.2 s) 500 A gG
Max. backup fuse (L) up to IK = 100 kArms (ta ≤ 5 s) 315 A gG
Nominal discharge current (8/20 µs) (In) 50 kA