top of page

Model

961125

Application recommend

L-N

TYPE

1

kA

50kA

Up

2.5 kV

Specification

DEHNbloc® modular

DB M 1 255 FM (961 125)

■ Coordinated spark-gap-based lightning current arrester consisting of a base part and a plug-in protection module

■ Maximum system availability due to RADAX Flow follow current limitation

■ Without additional cable length directly coordinated with DEHNguard surge protective device

Coordinated and modular single-pole lightning current arrester with high follow current limitation; with remote signalling contact for the monitoring system (floating changeover contact).

  • SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I 

  • Nominal voltage (a.c.) (UN) 230 V (50 / 60 Hz) 

  • Max. continuous operating voltage (a.c.) (UC) 255 V (50 / 60 Hz) 

  • Lightning impulse current (10/350 µs) (Iimp) 50 kA

  • Specific energy (W/R) 625.00 kJ/ohms 

  • Voltage protection level (UP) ≤ 2.5 kV

  • Follow current extinguishing capability (a.c.) (Ifi) 50 kArms

  • Follow current limitation / Selectivity

  • no tripping of a 32 A gG fuse up to 50 kArms (prosp.) 

  • Response time (tA) ≤ 100 ns

  • Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s) 500 A gG

  • Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s) 315 A gG

  • Max. backup fuse (L-L') 125 A gG

  • Temporary overvoltage (TOV) (UT) – Characteristic 440 V / 120 min. – withstand 

  • Operating temperature range (parallel connection) (TUP) -40 °C ... +80 °C 

  • Operating temperature range (series connection) (TUS) -40 °C ... +60 °C 

  • Operating state / fault indication green / red 

  • Number of ports 1 

  • Cross-sectional area (L/N, L'/N', N/PE (N)) (min.) 10 sq-mm. solid / flexible 

  • Cross-sectional area (L/N, N/PE(N)) (max.) 50 sq-mm.

  • Cross-sectional area (L'/N') (max.) 35 sq-mm.

  • 2 stranded / 25 sq-mm flexible 

  • For mounting on 35 mm DIN rails acc. to EN 60715 

  • Enclosure material thermoplastic, red, UL 94 V-0 

  • Place of installation indoor installation 

  • Degree of protection IP 20 

  • Capacity 2 module(s), DIN 43880

  • Approvals VDE, KEMA, UL 

  • Type of remote signalling contact changeover contact 

  • Switching capacity (a.c.) 250 V / 0.5 A 

  • Switching capacity (d.c.) 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A 

  • Cross-sectional area for remote signalling terminals max. 1.5 sq-mm. solid / flexible 

  • Use in switchgear installations with prospective short-circuit

  • Max. prospective short-circuit current 100 kArms (220 kApeak)

  • Limitation / Extinction of mains follow currents up to 100 kArms (220 kApeak)

  • Max. backup fuse (L) up to IK = 100 kArms (ta ≤ 0.2 s) 500 A gG

  • Max. backup fuse (L) up to IK = 100 kArms (ta ≤ 5 s) 315 A gG

  • Nominal discharge current (8/20 µs) (In) 50 kA


2.5 kV